| FE-50RU / FE-100RU |
All Engineering Data Pages FFE 50/100 RU Data Page
|
 |
|
Reflective Beam Detector The system is comprised of a single unit incorporating an infra-red transmitter and receiver. The signal generated in the transmitter element and reflected by the prism back to the receiver element is analyzed for the presence of smoke. The internal microprocessor determines an alarm condition when a predetermined level is reached. The system is designed to be mounted so the beam will project between 1ft. (0.305 m) and 2ft. (0.61m) below and parallel to the ceiling. Lateral detection may be up to 30ft. (9.144m) on either side of the beam, providing a maximum total coverage area of up to 19,800 square feet (60ft. x 330ft. or 18.288m x 100m).
Applications: Open areas where ceiling heights exceed 25ft. (Warehouses, Hotel Atriums, Industrial Plants and School Gymnasiums)
Public areas where cosmetics are of prime importance and detector heads need to be small and unobtrusive. (Shopping Malls, Libraries, Theaters and Churches)
|
Standard Features
- Models for ranges of
15 ft. to 160 ft. (5m to 50m)
160 ft. to 330 ft. (50m to 100m)
- Easy set up and alignment
- Single Compact Housing
- Calibrated obscuration test filter included
- 3 selectable alarm thresholds:
25%, 35% or 50%
- Microprocessor controlled
- Alarm latching or auto reset
- Automatic gain control
- 12 VDC or 24 VDC operation
- Separate alarm and trouble contacts
- Remote Test Station
|
|
Benefits: Reduces installation costs where 6 or more spot detectors are required in a single area. Reduces service time by taking advantage of optional remote test station located at ground level for system test without disruption of the site.
|
Specifications:
The reflective beam type smoke detector shall be a 4-wire 12/24 VDC device to be used with a Nationally Recognized Testing Labatory’s Listed separately supplied 4-wire control panel. Unit shall be listed to U.L. 268 and shall consist of an integrated transmitter and receiver. The detector shall operate between a range of 15 ft. to 330 ft. (5m to 100m). The UL Listed temperature range of the beam shall be 32°F to 100°F (0°C to 37.8°C). The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lenses. The unit shall include a wall mounting bracket. Testing shall be carried out by using a calibrated obscuration test filter. The Reflective beam type smoke detector shall be a Space Age Electronics, Inc. 50RU (160 ft./50m) or 100RU (330 ft./100m).
|
Electrical Specifications:
  Primary Input Power:
    10.2 to 30 VDC
  Standby Current:
    4mA @ 24VDC
  Alarm Current:
    15 mA @ 24 VDC
  Relay Contacts:
    1A at 30 VDC Resistive
  Reset Time:
    5 Seconds maximum
  Start Up Time:
    10 Seconds
  Optical Wavelength:
    880nm.
  Temperature Rating:
    -22°F to 131°F (-30°C to 55°C)
    32°F to 100°F (0°C to 37.8°C) UL
  Relative Humidity:
    10% to 93% RH non-condensing
  Range:
    50RU 15-160 ft. (5m to 50m)
    100RU 160-330 ft. (50m - 100m)
  Sensitivity:
    25%, 35%, 50%
  Dimensions:
    8.25” H x 4.5” D x 4.75” W
    (21.0cm H x 11.43cm D x
    12.065cm W)
  Unit shipping weight 3 lbs
Operational Specifications:
- Latching / Non Latching Alarm
- Fault condition (Trouble)
- 90% or more obscuration (Trouble)
- Automatic gain control
- Improper set up alignment (Trouble)
- Reflector targeting mode
- Microprocessor Controlled
- 3 Sensitivity Selections
- Alarm Indicator—Red LED
- Trouble Indicator—Amber LED
|
|
Approvals:
 UL UROX.S3417 ULC UROXC.S3417
 CSFM 7260-1508:102
MEA 70-02-E
|