| FFE-5000 |
All Engineering Data Pages FFE 5000 Data Page
|
 |
|
Self-Aligning Reflective Beam The Fireray 5000 System is an auto-aligning infrared beam smoke detector. Once the detector head is installed, using the easyfit mounting system, an integral LASER can be activated. This allows the reflective prism to be located quickly and with confidence. The AutOptimiser beam alignment system then takes over and automatically steers and maintains the beam in the optimum position for reliable performance. The signal generated in the transmitter element and reflected by the prism back to the receiver element is analyzed for the presence of smoke. The internal microprocessor determines an alarm condition when a predetermined level of obscuration is reached. The system is designed to be mounted so the beam will project between 1ft. (0.31m) and 2ft. (0.61m) below and parallel to the ceiling. Lateral detection may be up to 30ft. (9.144m) on either side of the beam, providing a maximum total coverage area of up to 19,800 square feet (60ft. x 330ft. or 18.29m x 100m). |
Standard Features
- Range of 26.25 ft. to 330 ft. (8m to 100m)
- AutOptimiser beam alignment system
- Ground Level System Controller
- LASER Assisted Prism Mounting
- AutOptimise Beam Alignment
- Electronic Obscuration Test
- Contamination Compensation
- Building Shift Compensation
- Separate alarm and trouble contacts
- Remote display and control unit with LCD backlight
- Password protected settings
- Programmable obscuration thresholds:
- 10% - 60% in 1% increments
- Programmable Fault and Alarm Timing:
- 2—30 Seconds
- 3 Year Warranty
|
|
 |
Specifications:
The projected beam type smoke detector shall be a 4-wire 24 VDC device to be used with a Nationally Recognized Testing Laboratory’s Listed separately supplied 4-wire control panel. Unit shall be listed to U.L. 268 and shall consist of an integrated transmitter/receiver and a remote control unit. The detector shall operate between a range of 26.25 ft. to 330 ft. (8m to 100m). The UL Listed temperature range of the beam shall be 32°F to 100°F (0°C to 37.8°C). The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lenses. The Reflective Beam shall include the AutoOptimise Beam Aligment feature to ensure the unit is always receiving the maximum signal available, and shall be able to compensate for building shift. The unit shall include a wall mounting remote display and control unit with LCD backlight.
Testing shall be carried out by using the UL approved internal obscuration test. The Reflective beam type smoke detector shall be an Space Age Electronics, Inc. Fireray 5000.
|
Electrical Specifications:
Primary Input Power:
14 to 28 VDC
Standby Current:
Low Current Mode: 12mA @ 24VDC
High Current Mode: 52mA @24VDC
Alarm Current:
52 mA @ 24 VDC
Relay Contacts:
1A at 30 VDC Resistive
Reset Time:
5 Seconds maximum
Start Up Time:
45 Seconds
Optical Wavelength:
850nm.
Temperature Rating:
-22°F to 131°F (-20°C to 55°C)
32°F to 100°F (0°C to 37.8°C) UL
Relative Humidity:
0% to 93% RH non-condensing
Range:
26.25ft. to 330ft. (8m to 100m)
Cableing Between Detector & Controller:
24—14 AWG 1—Pair Shieled
Sensitivity:
10% - 60% (35% Default)
Dimensions:
Head:
5.28” H x 5.31” L x 5.28” W
(135mm H x 134mm L x 132mm W)
Controller:
2.80” H x 9.25” L x 7.87” W
(71mm H x 235mm L x 200mm W)
Prism:
0.37” H x 4.13” L x 3.94” W
(9.5mm H x 105mm L x 100mm W)
Unit ship weight 5.75 lbs.
|
|
Approvals:


|
|