VSD Video Smoke Detection

FFE2000 Projected Beam Smoke Detector

FFE2000 Explosion proof Detector

FFE 50/100RU Reflective Beam Smoke Detector

FFE 50/100
Beam Accessories


FFE 5000 Self-Aligning Beam Smoke Detector

FFE 5000
Beam Accessories


SL-2000 Series Duct Smoke Detectors

SM-501 Series Duct Smoke Detectors

RT-3000 NEMA 4x Series Duct Smoke Detectors

SSU-SL-701-KIT
CO Duct Detectors


SSU-FASTTUBE
Duct Detector Test Kit


FFE-2000 EExd  All Engineering Data Pages FFE 2000 Data Page
Explosion Proof Projected Beam
The Fireray 2000 EExd is ideally suited to protect large areas with potentially explosive atmospheres, protection against smoking fires can be provided by this beam. Fireray 2000 EExd includes an infrared transmitter and a receiver, both of which are ATEX-certified for use in Group 2 hazardous areas (comparable to US CSA Certification for use in Class 1, Division 2, Groups A, B, C & D hazardous locations). There is a separate , safe area, wall-mounted remote low level control unit to allow adjustment and testing from a convenient non-hazardous location. The product is designed for large enclosures with oil rigs, refineries, ordinance stores, waste water treatment plants, and similar premises. It provides an early warning of smoldering smoke-generated fires, some of which may not be picked up by flame detectors installed in many hazardous areas. Smoke Detection If smoke is present in the beam’s path, the received signal is reduced by a level determined by the density of the smoke. If the smoke reduces the signal strength to between the obscuration threshold and 93% for more than 8 to 10 seconds, the fire alarm relay in the control unit is activated. The alarm threshold may be set to 25%, 35% or 50% to suite the installation.
Standard Features
  • Separate Transmitter and Receiver Units certified to EExd
  • Separate Transmitter and Receiver Units
  • Signal Strength indicating LED’s
  • Range 33ft. To 330ft. (10m to 100m)
  • Easy set up and alignment
  • Internal test switch
  • Conforms to BS5839 Part 5 EExd IIB T6
  • Calibrated obscuration test filter included
  • 3 selectable alarm thresholds: 25%, 35% or 50%
  • Microprocessor controlled
  • Alarm latching or auto reset
  • Automatic gain control
  • 12 VDC or 24 VDC operation
  • Separate alarm and trouble contacts
  • Ground Level Control Unit
  • Alignment by Universal Bracket
Operation:
The infrared signal is sent from the transmitter via an optical system. At 330 ft. (100m) the diameter of this infrared signal is approximately 10 ft. (3.05m). The wide angle beam arrangement simplifies alignment and increases stability. It is important that the projected beam smoke detector is positioned correctly to minimize the detection time. A fire alarm condition occurs when the smoke obscures the infrared beam. The time to detect a fire condition depends on the location of the smoke beam within the premises, the volume of smoke produced, the construction of the roof, and ventilation considerations.
Specifications:
The projected beam type smoke detector shall be a 4-wire 12/24 VDC device to be used with a Nationally Recognized Testing Laboratory’s Listed separately supplied 4-wire control panel. The unit shall consist of an integrated transmitter and receiver. The detector shall operate between the range of 33ft to 330ft (10m to 100m). The temperature range of the beam shall be –4ºF to +131ºF (-20ºCto +55ºC). The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lense. The beam detector shall be ATEX Certified, comply with BS5839 Part 5 and meet Eexd IIB T6 temperature range requirments. The unit shall include one wall mount alignment bracket. Testing shall be carried out by using a calibration test filter. The projected beam smoke detector shall be a Space Age Electronics, Inc. Fireray 2000 EExd.

Electrical Specifications:
   Primary Input Power
     11.5 to 30 VDC
   Protection:
     100ma Fuse in Control unit
   Standby Current
     8.5mA @ 24VDC
   Alarm Current
     16.5 mA @ 24 VDC
   Relay Contacts
     2A at 30 VDC, resistive
   Reset Time
     5 Seconds maximum
   Start Up Time (Automatic)
     45 Seconds
   Optical Wavelength:
     880nm.
   Temperature Rating:
     -4°F to +131°F (-20°C to +55°C)
   Relative Humidity:
     0% to 93% RH non-condensing
   Operational Range:
     33 ft.- 330 ft. (10m - 100m)
   RFI Immunity:
     10V/m @ KHz-1 GHz
   Field wiring size:
     14-24 AWG
   Sensitivity:
     25%, 35%, 50%
   Fire Alarm Thresholds:
     1.25dB (25%), 1.87dB (35%), 3dB (50%)
   Beam tolerance to misalignment at 35%:
     Transmitter +/- 1°
     Receiver +/- 4°
   Weight-Controller:
     4.00 lbs (1.8 kg)
   Weight-Transmitter/Receiver:
     8.8 lbs. (4 kg.)
   Dimensions-Controller:
     8.5” W x 10.5” H x 3.5” D
     (210mm W x 265mm H x 88mm D)
   Dimensions-Transmitter/Receiver (including mounting brackets):
     4.8” W x 4.8” H x 4.8” D
     (120mm W x 120mm H x 120mm D)
   Unit shipping weight 18.5 lbs.
Approvals:
ATEX Group 2
Sira 03ATEX1504
BS5839 Part 5 EExd IIB T6