Infinity Control Modules ICM Data Page
All Engineering Data Pages
The Infinity Control Modules are designed to maximize your flexibility in the field. The ICM units can be a used in a simple single fan stand-alone control element or with multiple fans, dampers and utilize units from the IAM series as well creating a sophisticated HVAC control center.

ICM component modules feature a Keyed or Rotary Switch fan/damper, On, Off, Auto control unit (ICMHOA), a key enabled ICMENGAGE switch supplies operating power to the HOA switches to prevent tampering by unauthorized individuals and the ICMLEDTEST switch allows for the testing of the visual annunciation on the ICMHOA switches.

The ICM units are designed to meet and exceed the requirements of NFPA 72 and UL 864 9th Edition. The ICM control/monitoring units are expandable in single gang increments and can be configured to provide precise control and monitoring functions. These design enhancements provide for greater capacity in large scale and complex control applications. Each controlled function must supply a feedback to the ICMHOA to meet the most stringent of specifications and code compliancy.
ICM

The control switch units shall be the Infinity Series ICM units manufactured by Space Age Electronics, Inc. The devises shall be manufactured under the requirements of NFPA 72 and UL 864 9th Edition. The ICMs shall be sized to fit a single gang electrical enclosure and be “gangable” to six units utilizing an appropriate IGB box and IGP plate.
The ICM units shall be enclosed in a .080” thick aluminum bracket with a .010” thick Lexan© cover including a viewing window for identification of the individual controlled devices.All field wiring shall be wired to clinch type terminals on all units.


Standard features:

  • Cover Switch Plates are scalable to meet your capacity
  • Utilizes standard Infinity IGP plates design that allows for adaptation to surrounding architectural design features (red, white, yellow and stainless steel available)
  • Legend sheet is protected by scratch resistant Lexan© window
  • Durable steel frame supports all operational devices in one to six gang electrical back boxes


Infinity IGP faceplates house 1 - 6 modules in standard or multiple gang electrical back boxes (refer to our IGB back boxes for housing up to 6 units).
Plate Box
Sequence Of Operation
The Red and Green LEDs provide positive feedback from the fan/damper sail/microswitches when wired to the status/monitor terminals on each ICMHOA unit. These LEDs may not light immediately, dependant on the speed of the fan or damper.


The ICMENGAGE switch is a manual method of keeping unauthorized/untrained individuals from tampering with the building’s HVAC systems. It does this by holding back operating power from the ICMHOAs until the key is activated.
The ICMLEDTEST is used to confirm the operational status of the ICMHOA’s LEDs.